Power Banks... Higher Charge Levels Linked to Greater Risk of Thermal Runaway and Ignition
Seoul Metropolitan Fire & Disaster Headquarters experiment: "The closer to fully charged, the greater the risk"
Batteries charged to 80-90% commonly distributed on the market
City to consult relevant ministries on "effective safety standards"
A study found that the higher the charge level of lithium-ion batteries used in power banks, the greater the risk of ignition when they are subjected to external pressure.
The Fire Investigation Research Center of the Seoul Metropolitan Fire & Disaster Headquarters released the results of a study on fire risks associated with the charge levels of lithium-ion batteries on the 16th.
The experiment was conducted following a fire at a logistics center in Incheon this past July, to assess the need to manage charge levels during the distribution and storage of lithium-ion batteries. It tested two types of batteries sold on the market: cylindrical and pouch-type. The charge levels were set at 30%, 50%, 70% and 100%, and pressure was applied using a pneumatic press.
Each charge level was tested five times. When fully charged, at 100%, both the cylindrical and pouch-type batteries experienced thermal runaway and ignition in four trials each. At 70%, both types showed venting, or the release of gas from inside the battery. Thermal runaway occurred in the cylindrical batteries, while a small flame was observed in the pouch-type batteries. No thermal runaway or ignition was observed at 50% or 30%.
The problem is that, in the absence of relevant regulations, batteries charged to high levels of 80-90% are commonly distributed. In air transport, to reduce fire risks, international standards require certain types of lithium-ion batteries to be shipped at a charge level of 30% or less.
Based on the results of this demonstration experiment, the Seoul Metropolitan Fire & Disaster Headquarters and the National Fire Agency plan to continue discussions with relevant government agencies on establishing safety standards, including the management of battery charge levels during distribution and storage.
Hot Picks Today
"Two Spend 500,000 Won in a Flash, Yet Wait Two Hours?" ... 'Dreamland' Shunned by Kids and Foreign Tourists
- The Era of Getting 200 Million Won After 30 Years Is Over... A Japanese Bank's "Perpetual Department Head" Who Just Clocked In Cries Out
- Spain Hit by Its Worst Tragedy... Lee Kangin, Moreno and Real Madrid Join Soccer World in Mourning
- They Said, “Make It Your Home for Life” - Then Suddenly Kicked 200 Passengers Off... What Happened to the Around-the-World Cruise?
- "130 Rice Bowls Sold Out in a Day"... 'Unfiltered Face' Adds 8 Million Won to Night Market Sales: China's Bungeunwoo
Hong Young-geun, head of the Seoul Metropolitan Fire & Disaster Headquarters, said, "The experiment confirmed that a battery's charge level can affect its fire risk. We will use scientific experiments and analysis to identify fire risk factors and build the evidence needed to establish effective safety management standards for batteries during distribution and storage."
© The Asia Business Daily. All rights reserved. Unauthorized AI training and use prohibited.